| Power rating | 
            3840 VA (240V) | 
          
          
            | Inlets | 
            Connection type | 
            2 x IEC-320-C20 connectors | 
          
          
            | Voltage and current rating | 
            100-240V (1 phase+neutral+protective conductor (protective ground)), 16А | 
          
          
            | Frequency | 
            50/60 Hz ± 5%  | 
          
          
            | Transfer time between inlets  | 
            From 3.5 to 14 ms | 
          
          
            | Grounding control  | 
            Indication of grounding presence/absence | 
          
          
            | Outlets | 
            Connector type | 
            10 x IEC-320-C13 connectors | 
          
          
            | Voltage and current rating | 
            100-240V (1 phase+neutral+protective conductor (protective ground)), 10А | 
          
          
            | Overcurrent and Short Circuit Protection Parameters | 
            Overload protection: configurable 0.1-10 A (default setting 10 A)
               Short circuit protection: 7-17 x iNom (triggers at a short-circuit current of 75A) | 
          
          
            | Power consumption metering | 
            Separate power consumption metering on each outlet | 
          
          
            | Power-on delay between outlets | 
            Programmable (default delay 1 second) | 
          
          
            | Cords fixation | 
            Power cables fixation kit (option) | 
          
          
            |  Indicator lights | 
            Inlet state | 
             - On/Off/Incorrect inlet voltage/Priority
                - Current/Voltage
                - Grounding indication presence/absence
             | 
          
          
            | Сhannels (outlets) state | 
            On/Off/Short circuit/Outlet overcurrent/Inlet overcurrent | 
          
          
            | Remote control and remote monitoring | 
            Inlet state  | 
             - On/Off/Incorrect inlet voltage/Priority
                - Frequency/ Voltage/ Current/ Wattage
                - Grounding indication presence/absence
             | 
          
          
            | Channels state | 
             - On/Off/Short circuit/Outlet overcurrent/Inlet overcurrent
                - Managing current cutoff thresholds and power-on delay
             | 
          
          
            | Power consumption metering | 
            Separate power consumption metering on each outlet | 
          
          
            | Supported protocols | 
             - HTTP/HTTPS (WEB Interface/REST API)
                - SSH
                - SNMPv1, SNMPv2c, SNMPv3, SNMP Traps
                - SMTP
                - RADIUS
             | 
          
          
            | Automation (Watchdog) | 
             - Output channel (outlet) reset, if there are no responses to ICMP requests (pings)
                - Output channel (outlet) reset, if the TCP port is unavailable
                - Output channel (outlet) reset, when the current decreases
                - Output channel (outlet) reset, if the miners hash rate decreases
             | 
          
          
            | Standards compliance | 
            Electromagnetic compatibility | 
            CE (EN55032, EN55024, EN61000)
               EAC (GOST30804 (IEC61000), GOST51317 (IEC61000)) | 
          
          
            | Safety | 
            СЕ (EN60950), EAC (GOST51321 (IEC60439)) | 
          
          
            | General parametres | 
            Communication interface | 
            Ethernet 10/100 Mbps | 
          
          
            | Accessories included | 
            Fixtures for installation in a 19 inch rack, 2 x inlet cables (C20 to Euro/Schuko) 2.0m, quick install guide | 
          
          
            | Available options | 
            Extended fixtures for installation in a 19 inch rack, power cable organizer | 
          
          
            | Size (width x depth x height) | 
            440 x 365 x 44 mm, takes a standard 1U slot in a 19 inch rack | 
          
          
            | Module weight/included accessories/total weight with packaging (kg) | 
            5.2/1.21/8.13 | 
          
          
            | Operating temperature | 
            0 ~ +40 °С | 
          
          
            | Storage temperature | 
             -20 ~ +60 °С | 
          
          
            | Operating humidity | 
            45 ~ 85 % (no condensation) | 
          
          
            | Cooling | 
            Passive | 
          
          
            | Noise level | 
            Under 30 dBA (powering on/off and switching ports) | 
          
          
            | Default Warranty | 
            1 year |